Product Description
The TMP2 series heat detectors include electronic circuits for signal conditioning generated by the transducer. The electrical signal is transformed into an engineered output with different interface solutions. The electronic card, reduced to the minimum size, is made using SMT technology and placed directly into the unit probe. They are sturdy, shock and vibration resistant, and are compatible with any fire alarm control panel on the market. TMP2 detectors are particularly suitable in dangerous environmental conditions such as the presence of corrosive elements or condensing steam.
TMP2 (4-20mA output): ATEX II 2 G Ex d IIC T6 heat detector with proportional 4-20mA output and a temperature range of -10 ° to 100 °C (-10 °=4mA + 100 °=20mA); IP65 aluminum alloy housing; chrome plated brass probe (stainless steel available); one 3/4′′ NPT way connection on the probe side.
ATEX Zone 1 certified II 2G Ex d IIC T6 and EN54-5 certified heat detectors for temperatures A2 (54° to 70°C) and C (84° to 100°C) ; rate of rise and/or static alarm; OR PULSE in normal operating conditions, OFF in fault condition, ON in alarm condition; OR PULSE in normal operating conditions; OR PULSE in normal operating conditions; OR PULSE in normal operating conditions; OR PULSE in normal operating conditions;can be automatic or manual. The JO model has one 1/2′′ NPT connection on the side opposite the probe, while the TO model has two 1/2′′ NPT connections on both sides.
TMP2-Config is a new diagnostic and configuration software for the monitoring of sensors and detector functions, Alarm Temperature Levels setting, Temperature Class setting according to EN54-5, Static or Rate of Rise functionality setting, LED functioning mode setting, Alarm Status setting (Latched or Reflex), Service Time Counter, Number of Events Counter, and General Information: sensor status, reset, number of power ON and power OFF.
Application Example
The TMP2 electronic heat detector can be applied to the following fields:
- Commercial and industrial plants
- Hazardous areas (Classified Zones 1/21 and 2/22)
- Suitable in dangerous environmental conditions such as in presence of corrosive elements or condensing steams
- Suitable to be used with all conventional fire detection systems
Especially suitable for:
- Refineries and hazardous material stores
- Extraction ducts
- Boiler rooms
- Workshops
- Oil & gas plants
- Pumping rooms
- Refrigeration cells